Pulsafeeder MPC Vector Manual de usuario Pagina 33

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 70
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 32
27
11. Press the UP and/or DOWN arrow keys to adjust the Max Current setpoint.
M A X S E T P T 2 0 . 0 M A
F L O W : 4 . 0 0 G P M
12. Press ENTER to accept the Current Setpoint. The cursor will blink on the bottom line indicating that the
Flow setpoint may be adjusted.
13. Press the UP and/or DOWN arrow keys to adjust the Max Flow setpoint.
M A X S E T P T 2 0 . 0 M A
F L O W : 5 . 9 2 G P M
You may back out of the DRY calibration routine at any point up to now without saving any calibration
settings by pressing the MENU key several times.
1. Press the ENTER key to save the new Analog Calibration values. Upon completion of
Calibration you should see the following screen.
A N A L O G I N P U T
C A L I B R A T E D
2. Press the MENU key several times to return to Operations Mode.
Vista de pagina 32
1 2 ... 28 29 30 31 32 33 34 35 36 37 38 ... 69 70

Comentarios a estos manuales

Sin comentarios